Electrical Tutorial - Service Types
Home RedDomains.com Education Center Inspectors Find an Inspector Buyers & Sellers

Home
Up
Site Map
Store
About Us
Specials
Events
News
Links
Privacy Policy
Contact Us
Technical Support
Manual & FAQ

MSI International, Inc.
Est. 1992

 


Request Demo

 


Request Demo



Request Demos



 

 

 

 

 


Software
XL Pro
MasterCheckList Pro
HomeTrex
TexTrex Pro
iNACHI Reporter

 

 

 

Other
MSI International
Sites

LearnSmith.Net
Education Center


Find an Inspector
 

#1 Home Inspection sales leader on eBay 8 years in a row!

 

 

 

 

 

 

RedDomains.com
Domain Names
Website Hosting


Find an Inspector

 

 

Determining the Size and Type of an Electrical Service

This is an excerpt from one of my advanced electrical courses for home and commercial building inspectors.  I have modified it slightly for this tutorial.   

George wells, BSEE, MBA, CMI, Licensed Master Electrician

 

Knowing the number or size of conductors entering a building does not provide enough information to determine the Voltage, number of phases, or the capacity of the electrical service.  Single-phase services will usually have two to four conductors.  Two-phase services will usually have three to five conductors, and three phase services will usually have three to five conductors.

The capacity ratings of smaller electrical services, such as in houses, are usually listed in Amperes.  The capacity ratings of larger electrical services are usually listed in kVA and mVA.

Whenever possible, look at the transformer connections to determine the number of phases, Voltages, and capacity of the electrical service.

There are at least five distinct arrangements possible with a service drop having four conductors.  The service can be Single-phase, Two-phase, or Three-phase.  The five possibilities of a four wire service entrance are Single-phase, Two-phase, Three-phase center-tapped Delta, Three phase corner-grounded Delta, and Three-phase Wye.

Unless otherwise noted, references to transformer connections are for the secondary side; in other words, the side to which the service conductors are connected.


1.  Single-phase

I've encountered four wire arrangements many times.  It is not an arrangement that an inspector is likely to see in a residential electrical system but it was a popular arrangement in the late 1970’s and the early 1980’s on small and medium commercial installations.  

Major computer companies in the late 1970’s and early 1980’s where demanding floating grounds for the mini-computers (not micro-computers, aka PC’s) that were being installed in small commercial facilities.  As an electrician in the 1970’s and 1980’s I could not reconcile the demands of the computer makers with the requirements of the NEC, the NESC and IEEE Red Book and Green Book guidelines for power distribution and grounding.  At that time FIPS Pub 94, and today the IEEE Emerald Book, would have four conductors going back to the transformer in a perfect world. 

A generally accepted compromise was to carry a fourth conductor back to the transformer.  By the end of the 1980’s the computer companies had stopped asking for floating grounds.

Inspectors and even electricians sometimes mistakenly referred to three-wire single-phase systems as Two-phase.  A Single-phase system has a center tap on the secondary side of the transformer to develop a neutral.  Therefore, it is a split-phase system, not two-phase.  The actual secondary Voltage of transformer supplying a modern residential electrical system is 240V.  Adding a center tap provides the two 120V sides and a neutral conductor.  The neutral conductor is solidly grounded.


2.  Two-phase

A single-phase system has phase legs that are 180 electrical degrees apart.  A two-phase system has phase legs that are 90 electrical degrees apart.  It is possible for a two-phase system to have only three conductors but that is not the usual practice because, unlike single-phase and three phase systems, the phases are not symmetrical so there is no true neutral.   

Electricians and inspectors on the West coast may have never seen a two-phase four-wire system but the farther Northeast you go, the more likely you are to encounter them.  There was only one major installation of two-phase generation in the Western United States.  In California, the Pacific Power and Light Company installed a two-phase system in San Gabriel Canyon, near Los Angeles, to serve the town of Azusa. I don’t know when that system was taken out of service.

Most of the two-phase systems were taken out of service by 1980.  There are no major two-phase systems currently in use in the US by public utility companies but there still thousands of privately owned systems throughout the US.  Privately owned systems include those that buy primary power from a public utility and redistribute it.

Two single-phase transformers connected in a “T” connection, also known as a “Scott” connection can be used to convert the two-phase to three-phase once inside the building.

A traditional Two-phase system has four wires.  Two-phase five-wire systems are, strictly speaking, not two-phase systems.  They are four-phase systems but they are known as Two-phase five-wire systems.

Two-phase systems have been almost universally retrofitted to either single-phase or three phase.  The presence of the fourth conductor on a commercial building could indicate that a two-phase system has been retrofitted to a single-phase system.  As I mentioned earlier, Single-phase systems are sometimes mistakenly referred to as two-phase.

 

3. Three phase

Three-phase systems have three symmetrical phases.  That is, the phases are an equal 120 electrical degrees apart.  A three-phase system requires neither a ground nor a neutral to be able to function properly.  At any given time, in a properly balanced Three-phase system, two of the three phase conductors serve as the return path for the current. 

  1. Wye

This has become the most popular secondary connection in small to medium size interior electrical distribution systems because its center tapped neutral enables it to provide a wide range of useful Voltages and handle a wide variety of loads.

You can explore the relationship of the currents in the phases to the current in the neutral of a Wye system by entering various values in my 3p4w Neutral Current Calculator.

  1. Ungrounded Delta

The Ungrounded Delta is NOT one of the five possible arrangements of a typical four-wire service.  I have listed it here to demonstrate further why it is not possible to determine the number of phases based on the number of conductors.  An ungrounded system would typically have the three ungrounded conductors and a messenger cable but the messenger cable would not enter the building.  It is possible, however, that an overly zealous electrician or facility manager would connect it to an electrode as a supplementary grounding electrode.  There would be nothing wrong with doing that.

Delta systems may or may not have neutral conductor but they do not require a neutral because the phases are symmetrical (120 electrical degrees apart).  The Ungrounded Delta is still very popular for both the primaries and secondaries of substations; particularly, privately owned substations.

Most ungrounded Deltas are connected in a Delta Wye configuration.  It is called an Ungrounded Delta because it is not grounded on the primary.  Even though it is called an “Ungrounded Delta”, there is a ground on the secondary at the center of the Wye.

In instances where there is an Ungrounded Delta secondary, the neutral is developed in a separately derived system downstream of the substation.  This is still probably the most popular choice for manufacturing facilities.

c. Delta with a corner ground

Corner grounded Delta’s are no longer common in new installations but there still thousands of existing installations.  Their purpose was to stabilize Voltages and reduce the cost of the system.

  1. Delta with a center tap ground

Known by a variety of names such as “Hi-leg”, Wild-leg”, “Stinger”, B-phase” and “Red-leg”.  The high leg is usually colored orange, red, or brown.  Local customs vary.  In some locations even yellow is used to identify the high leg.   

Center tapped Delta systems are still in wide use but are becoming less popular.  The Voltages present in a center-tapped Delta often confuse less experienced electricians.  It is easy for an inexperienced electrician to mistake the center-tapped Delta for a Wye connection because of the Voltage relationships.

  1. Open Delta

The Ungrounded Delta is NOT one of the five possible arrangements of a typical four-wire arrangement.  I have listed it here to demonstrate further why it is not possible to determine the number of phases based on the number of conductors.

Open Deltas are used to keep costs down or to operate a three phase system at reduced capacity when one of the transformers in a three single-phase transformer arrangement is lost.  The general rule is that the system will run at 57.7% of capacity with two Single-phase transformers.  However, additional cooling with fans can often increase the capacity.

 

 

BestInspectors.Net  Store
Inspection Report Software, Tools, Books, CD's

The Inspector Store
A service of
BestInspectors.Net and Amazon.com
Tools, Books, CD's, Videos

If it has anything to do with Home Inspection,
You'll probably find it here

Home and Commercial Inspection Report Software

 

Also

The Home Inspection Store

 

 

Home Up Site Map Store About Us Specials Events News Links Privacy Policy Contact Us Technical Support Manual & FAQ